7, 10, 13 and 16 kW
Air-Cooled Standby Generators
All Guardian generators are UL Listed.
|
| 7 kW |
10 kW |
13 kW |
16 kW |
- 7,000 Watts
- Circuits: 8
- Generac 410cc OHVIŽ Engine
|
- 10,000 Watts
- Circuits: 10
- Electronic Governor
- Generac 530cc OHVIŽ Engine
|
- 13,000 Watts
- Circuits: 12
- Electronic Governor
- Generac 992cc OHVIŽ Engine
|
- 16,000 Watts
- Circuits: 16
- Electronic Governor
- Generac 992cc OHVIŽ Engine
|
Generator Set
| Model Number |
5240 |
5241 |
5242 |
5243 |
| Rated Power (LP / NG) |
7/6 kW |
10/9 kW |
13/13 kW |
16/15 kW |
| Rated Amps @ 60
Hz |
|
|
|
| 240 V, 1Ř (LP / NG)
|
29.2/25 |
42/38 |
54/54 |
67/63 |
| 3 Phase Models
|
NA |
NA |
NA |
NA |
| Surge Watts - 240V, 1 Ř
|
11,040 |
15,120 |
22,800 |
28,080 |
| Surge Amps |
46
|
63 |
95 |
117 |
| Engine
(Generac OHVI)
|
410 cc /
Single |
530cc /
V-Twin |
992cc /
V-Twin |
992cc /
V-Twin |
| Alternator RPM |
3600
|
3600 |
3600 |
3600 |
| Enclosure |
Steel |
Steel |
Steel |
Steel |
| Whisper Test |
No |
No |
No |
Yes |
| Sound Level (dBA @
exercise) |
62 |
63 |
66 |
60 |
| (dBA @ normal
operation) |
62 |
63 |
66 |
66 |
| Dimensions (L" x W" x H")
|
48x24x28 |
48x24x28 |
48x24x28 |
48x24x28 |
| Automatic Transfer Switch
(included) |
100 Amp / 8 circuit |
100 Amp / 10 circuit |
100 Amp / 12 circuit |
100 Amp / 16 circuit |
| Weight |
336
|
375 |
426 |
445 |
| |
|
|
|
|
| |
|
|
|
|
|
Control Set |
|
|
Engine Start Sequence |
Cyclic cranking: 7 sec.
on, 7 sec. rest. 90 sec. maximum duration |
|
Automatic Low Oil Shutdown |
Standard |
|
Overspeed Shutdown |
Standard, 72 Hz |
|
Overcrank Protection |
Standard |
|
Automatic Voltage Regulator with Over-Voltage
Protection |
Standard |
|
Engine Warmup |
10 seconds |
|
Engine Cool-Down |
1 minute |
|
Safety Fuse |
Standard |
|
2.5 Amp Timed Trickle Battery Charger |
Standard |
|
Auto Switch |
Automatic start on utility failure/7 day
exercise |
|
Off Switch |
Stops unit. Power is removed. Control and
charger still operate |
|
Manual / Test (start) |
Start with starter control, unit stays on.
If utility fails, transfer to load takes place
|
|
Full Monitoring System |
Oil pressure, coolant temperature, engine
speed, coolant level, cranking time, starter
lockout, utility sensing |
|
Shutdown and LED Indicators
|
overspeed and overcrank, low oil pressure,
high coolant temperature, low coolant level, low
fuel pressure, low battery voltage |
|
Transfer Switch |
|
| No. of Poles |
2 |
| Current Rating
(amps) |
100 |
| Voltage Rating (VAC) |
250 |
| Utility Voltage Monitor
(fixed) |
| - Pick-up
|
70% |
| - Drop
out |
60% |
|
| Return to Utility |
Approx. 13 seconds |
| Exercised 7
minutes weekly |
Standard |
| UL Listed |
Yes |
| Enclosure Type |
NEMA 1 (Indoor rated only) |
| Dimensions (H" x
W" x D") |
26.5 x 12.5 x 7 |
|
|